APD 2500 BD

Product: BAUDOUIN Alternator: AK 72000 CONTROL SYSTEM: DSE 7320
INTRODUCTION

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.


*The indicated PRP Power is for reference only. This engine is designed for emergency standby power (ESP) applications only.

General Characteristics
Model Name APD 2500 BD
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model BAUDOUIN - 20M33G2500/5
Alternator Made and Model Aksa - AK 72000
Control Panel Model DSE 7320
Canopy AK 100 - 2500BD
3 Phase, 50 Hz, PF 0.8
VOLTAGE STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 2500 2000.00 2250 1800.00 3608.55
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine BAUDOUIN
Engine Model 20M33G2500/5
NO. OF CYLINDERS AND BUILD 20 cylinders - V type
BORE AND STROKE mm 150 X 185
TOTAL DISPLACEMENT L 65.4
Aspiration Turbo Charged and Aftercooled(Air to Water)
COMPRESSION RATIO 15:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 235
Standby Power (kW/HP) 2210/2964
Block Heater QTY
2
Block Heater Power (Watt)
3000
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
HPCR (High Pressure Common Rail)
Governor System
ECU
Operating Voltage (Vdc)
24 Vdc
Battery and Capacity (Qty/Ah)
4x200
Charge Alternator (A)
55
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min)
2040
Coolant Capacity (engine only) (l)
140
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
466.4
Fuel Cons. Prime With %75 Load (lt/hr)
360.7
Fuel Cons. Prime With %50 Load (lt/hr)
240.5
ALTERNATOR SPECIFICATIONS
Manufacturer Aksa
Alternator Made and Model AK 72000
Frequency (Hz) Hz 50
Power (kVA) kVA 2500
DESIGN   Brushless
VOLTAGE V 400
Phase 3
A.V.R. MX341
Voltage Regulation (+/-) 1
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 4760
COOLING AIR (m³/min) m3 161.4
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
6760 2240 2842
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AK 100 - 2500BD
9633 2800 3457 2200
OPTIONAL EQUIPMENTS Engine

- Fuel-Water Seperator Filter

- Oil heater

Alternator

- Anti-Condensation Heater

- Over sized alternator

- PMG excitation + AVR

- Main line circuit breaker

Canopy

- Galvanized Coating

- ISO Container

- Marine Grade Paint

Control Panel

- Automatic synchronising and power control system (Multi gen-set Parallel)

- Parallel system with mains

- Transition synchronization with mains

- Alarm output relays

- Earth fault, single set

- Parallel system with mains

- Remote relay output

- Remote communication with modem

- Charge Ammeter

Transfer Panel

- Three or four pole contactor

- Three or four pole motor operated circuit breaker

Auxiliary Equipment

- Main Fuel Tank

- Automatic or manual fuel filling system

- Electrical or manual oil drain pump

- Low and high fuel level alarm

- Inlet and outlet motorized louvers

- Inlet and outlet acoustic baffles

- Tool kit for maintenance

- 1500/3000 hours maintenance kit

- Supplied with oil and coolant (-30°C)

Exhaust

- Residential Silencer

- Silencer Spark Arrester

- Critical Silencer

- Catalytic Convertor

CONTROL SYSTEM: DSE 7320
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices

DSE model 7320, Auto Mains Failure control module, with a highly sophisticated level of new features and functions

Static battery charger, Fuses for control circuits

CONSTRUCTION and FINISH

- Components installed in sheet steel enclosure.

- Phosphate chemical, pre-coating of steel provides corrosion resistant surface

- Polyester composite powder topcoat forms high gloss and extremely durable finish

- Lockable hinged panel door provides for easy component access

INSTALLATION

The Control panel is mounted at the generating set baseframe on robust steel stand or power module. Located at side

of generating set with properly panel visibility.

GENERATING SET CONTROL UNIT

- The DSE 7320 control module is a standard addition to our generator sets from 220 kVA upwards and it has been

designed to start and stop diesel and gas generating sets that include electronic and non electronic engines.

- The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable

for controlling a standby generating set in conjunction with an automatic transfer switch.

- The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and

indicating faults by means of its LCD display on the front panel.


Instruments
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due

GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence

MAINS
Voltage (L-L, L-N)
Frequency

Options

- High oil temperature shut down

- Low fuel level shut down

- Low fuel level alarm

- High fuel level alarm

Standards

- Electrical Safety / Electro Magnetic Compatibility (EMC)

- BS EN 61000-6-2 EMC Generic Immunity Standard

- BS EN 61000-6-4 EMC Generic Emission Standard

- BS EN 60950 Electrical Safety

STATIC BATTERY CHARGER

- Battery charger is manufactured with switching-mode and SMD technology and it has high efficiency.

- Battery charger models' output V-I characteristic is very close to square

- 2405 has fully output shot circuit protection and it can be used as a current source.

- 2405 charger has high efficiency, long life, low failure rate, light-weight and low heat radiated in accordance

with linear alternatives.

- The charger is fitted with a protection diode across the output.

- Charge fail output is available.

- Connect charge fail relay coil between positive output and CF output.

- Input: 196-264V.

- Output: 27,6V 5A or 13,8V 5A.

Canopy: AK 100 - 2500BD
STANDARD SPECIFICATIONS


CANOPY MODEL AK 100 - 2500BD
WIDTH mm. 2800
LENGTH mm. 9633
HEIGHT mm. 3457
TANK CAPACITY (lt.) Lt. 2200